Generac · Generator Moderate

1906 — Loss of AC Sense

Controller can no longer sense generator AC output even though engine is running. Often a wiring issue between the alternator and controller, or a failed sense circuit.

Keep using it?
Yes, with caution
DIY difficulty
Moderate
Verified against
generac.com ↗

How to fix it

  1. Press the main line breaker on the generator firmly to OFF then back to ON.
  2. Power down, pull controller fuse, and reseat the AC sense connector at the controller.
  3. Measure AC output at the alternator with a multimeter while running in Manual — should be 240V at no-load.
  4. If 0V output, AVR or stator has failed — call dealer.

Why it happens

Typical signs: 1906 fault · Engine running but unit does not transfer · No AC voltage at the panel

  • Tripped main line circuit breaker on the generator First thing to check — breaker on the side/back of the unit popped open.
  • Loose AC sense wiring at controller Connector backed out of the controller.
  • Failed AVR No output to sense.
  • Failed stator Open or shorted stator winding.

Parts you may need

If diagnosis points to a failed part, these are the common replacements. As an Amazon Associate we earn from qualifying purchases.

  • Main line circuit breaker Common replacement
    Amazon →

More Generac generator codes

All Generac codes → All generator codes →

Always unplug an appliance before servicing it. This guide is for informational purposes and is not a substitute for a qualified technician. Verified against manufacturer documentation: generac.com.